C10B6TM063 Circuit breaker, ComPacT NSX100B, 25kA/415VAC, 4 poles 3D (neutral not protected), TMD trip unit 63A

Category:

C10B6TM063 Circuit breaker, ComPacT NSX100B, 25kA/415VAC, 4 poles 3D (neutral not protected), TMD trip unit 63A

Main
RangeComPacT
Product nameComPacT NSX
Device short nameNSX100B
Product or component typeCircuit breaker
Device applicationDistribution
Poles description4P
Protected poles description3D
Neutral positionLeft
[In] rated current63 A at 40 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
Network typeAC
Network frequency50/60 Hz
Suitability for isolationYes conforming to EN/IEC 60947-2
Utilisation categoryCategory A
Breaking capacity40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeB 25 kA 415 V AC
Trip unit nameTM-D
Trip unit technologyThermal-magnetic
Trip unit protection functionsLI
control typeToggle
Circuit breaker mounting modeFixed
Complementary
[Ui] rated insulation voltage800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Ics] rated service breaking capacity40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
7 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability50000 cycles
Electrical durability50000 cycles at 440 V In/2
30000 cycles at 440 V In
20000 cycles at 690 V In/2
10000 cycles at 690 V In
Power dissipation per pole8.61 W
Mounting supportBackplate
Mounting positionHorizontal and vertical
Flat on the back
Upside connectionFront
Downside connectionFront
Connection pitch35 mm
Protection typeL : for overload protection (thermal)
I : for short-circuit protection (magnetic)
Trip unit rating63 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection)Adjustable
[Ir] long-time protection pick-up adjustment range0.7…1 x In
Long-time protection delay adjustment type trFixed
[tr] long-time delay adjustment range120…400 s at 1.5 x In
15 s at 6 x Ir
Neutral protection settingNo protection (3D)
Instantaneous protection pick-up adjustment type IiFixed
[Ii] instantaneous protection pick-up adjustment range500 A
Earth-leakage protectionWithout
Number of slots5 slot(s)
Width (W)140 mm
Height (H)161 mm
Depth (D)86 mm