Specification:
| range of product | Harmony XB4 |
|---|---|
| product or component type | Selector switch |
| device short name | XB4 |
| bezel material | Chromium plated metal |
| fixing collar material | Zamak |
| mounting diameter | 0.87 in (22 mm) |
| sale per indivisible quantity | 1 |
| head type | Standard |
| shape of signaling unit head | Round |
| type of operator | stay put |
| operator profile | Black standard handle |
| operator position information | 2 positions 90° |
| contacts type and composition | 1 NO + 1 NC |
| contact operation | Slow-break |
| connections – terminals | Screw clamp terminals, <= 2 x 1.5 mm² with cable end EN/IEC 60947-1 Screw clamp terminals, >= 1 x 0.22 mm² without cable end EN/IEC 60947-1 |
| height | 1.85 in (47 mm) |
|---|---|
| width | 1.18 in (30 mm) |
| depth | 2.68 in (68 mm) |
| terminals description ISO n°1 | (13-14)NO (21-22)NC |
| net weight | 0.23 lb(US) (0.105 kg) |
| resistance to high pressure washer | 1015.26 psi (7000000 Pa) 131 °F (55 °C) 0.1 m |
| contacts usage | Standard contacts |
| positive opening | With EN/IEC 60947-5-1 appendix K |
| torque value | 1.24 lbf.in (0.14 N.m) NO changing electrical state |
| mechanical durability | 1000000 cycles |
| tightening torque | 7.08…10.62 lbf.in (0.8…1.2 N.m) EN 60947-1 |
| shape of screw head | Cross Philips no 1 Cross pozidriv No 1 Slotted flat Ø 4 mm Slotted flat Ø 5.5 mm |
| contacts material | Silver alloy (Ag/Ni) |
| short-circuit protection | 10 A cartridge fuse gG EN/IEC 60947-5-1 |
| [Ith] conventional free air thermal current | 10 A EN/IEC 60947-5-1 |
| [Ui] rated insulation voltage | 600 V 3)EN 60947-1 |
| [Uimp] rated impulse withstand voltage | 6 kV EN 60947-1 |
| [Ie] rated operational current | 3 A 240 V, AC-15, A600 EN/IEC 60947-5-1 6 A 120 V, AC-15, A600 EN/IEC 60947-5-1 0.1 A 600 V, DC-13, Q600 EN/IEC 60947-5-1 0.27 A 250 V, DC-13, Q600 EN/IEC 60947-5-1 0.55 A 125 V, DC-13, Q600 EN/IEC 60947-5-1 1.2 A 600 V, AC-15, A600 EN/IEC 60947-5-1 |
| electrical durability | 1000000 cycles, AC-15, 2 A 230 V 3600 cyc/h 0.5 EN 60947-5-1 appendix C 1000000 cycles, AC-15, 3 A 120 V 3600 cyc/h 0.5 EN 60947-5-1 appendix C 1000000 cycles, AC-15, 4 A 24 V 3600 cyc/h 0.5 EN 60947-5-1 appendix C 1000000 cycles, DC-13, 0.2 A 110 V 3600 cyc/h 0.5 EN 60947-5-1 appendix C 1000000 cycles, DC-13, 0.5 A 24 V 3600 cyc/h 0.5 EN 60947-5-1 appendix C |
| electrical reliability | Λ < 10exp(-6) 5 V 1 mA in clean environment EN/IEC 60947-5-4 Λ < 10exp(-8) 17 V 5 mA in clean environment EN/IEC 60947-5-4 |
| device presentation | Complete product |
| protective treatment | TH |
|---|---|
| ambient air temperature for storage | -40…158 °F (-40…70 °C) |
| ambient air temperature for operation | -40…158 °F (-40…70 °C) |
| overvoltage category | Class I IEC 60536 |
| IP degree of protection | IP69 IP69K IP67 IEC 60529 |
| NEMA degree of protection | NEMA 13 NEMA 4X |
| standards | EN/IEC 60947-5-5 JIS C8201-5-1 UL 508 EN/IEC 60947-5-4 EN/IEC 60947-1 CSA C22.2 No 14 EN/IEC 60947-5-1 JIS C8201-1 |
| product certifications | DNV LROS (Lloyds register of shipping) CSA GL UL RINA BV |
| vibration resistance | 5 gn 2…500 Hz)IEC 60068-2-6 |
| shock resistance | 30 gn 18 ms) half sine wave acceleration IEC 60068-2-27 50 gn 11 ms) half sine wave acceleration IEC 60068-2-27 |