Specification:
range |
TeSys
|
---|---|
product name |
TeSys T
|
device short name |
LTMR
|
product or component type |
Motor controller
|
device application |
Equipment monitoring and control
|
measurement current |
0.4…8 A
|
[Us] rated supply voltage |
24 V DC
|
current consumption |
56…127 mA
|
supply voltage limits |
20.4…26.24 V DC
|
communication port protocol |
Modbus TCP/EtherNet/IP
|
bus type |
Ethernet IEEE 802.3 interface, addressing 0…159, transmission rate 10…100 Mbit/s, RJ45 with 2 shielded twisted pairs
|
[Ui] rated insulation voltage |
690 V conforming to EN/IEC 60947-1
690 V conforming to CSA C22.2 No 14 690 V conforming to UL 508 |
---|---|
[Uimp] rated impulse withstand voltage |
6 kV current or voltage measurement circuit conforming to EN/IEC 60947-4-1
0.8 kV communication circuit conforming to EN/IEC 60947-4-1 0.8 kV supply, inputs and outputs conforming to EN/IEC 60947-4-1 |
short-circuit withstand |
100 kA conforming to EN/IEC 60947-4-1
|
associated fuse rating |
4 A gG for output
0.5 A gG for control circuit |
protection type |
Phase failure
Locked rotor Earth-leakage protection Thermal protection Overload Phase unbalance Reverse polarity protection Power factor variation Overload (long time) Thermal overload protection Load fluctuation |
network and machine diagnosis type |
Event recording
Remaining operating time before overload tripping Trip context information Waiting time after overload tripping Running hours counter/operating time Trip history information Fault recording Starting current and time Phase fault and earth fault trip counters Motor control command recording |
logic input number |
6
|
input current |
7 mA
|
current state 0 guaranteed |
Logic input: < 5 V and <= 15 mA for 5 ms
|
current state 1 guaranteed |
Logic input: < 15 V and 2…15 mA for 15 ms
|
maximum output switching frequency |
2 Hz
|
load current |
5 A at 250 V AC for logic output
5 A at 30 V DC for logic output |
permissible power |
480 VA (AC-15), Ie = 2 A, 500000 cycles (output)
30 W (DC-13), Ie = 1.25 A, 500000 cycles (output) |
maximum operating rate |
1800 cyc/h
|
contacts type and composition |
1 NO + 1 NC fault signal
3 NO |
metering type |
Average current Iavg
Temperature Earth-fault current Phase current I1, I2, I3 RMS Imbalance current |
measurement accuracy |
5…15 % earth fault current internal measurement (for current > 0.1 A)
1 % voltage (100…830 V) 3 % power factor (cos φ > 0.6) 5 % earth fault current external measurement (< 5 % or 0.01 A) +/- 30 min/year internal clock 0,02 temperature 1 % current 5 % active and reactive power |
overvoltage category |
III
|
connection pitch |
5.08 mm
|
connections – terminals |
Control circuit: connector 1 cable(s) 0.25…2.5 mm² (AWG 24…AWG 14) flexible with cable end
Control circuit: connector 1 cable(s) 0.2…2.5 mm² (AWG 24…AWG 14) flexible without cable end Control circuit: connector 1 cable(s) 0.25…2.5 mm² (AWG 24…AWG 14) flexible without cable end Control circuit: connector 1 cable(s) 0.2…2.5 mm² (AWG 24…AWG 14) solid without cable end Control circuit: connector 2 cable(s) 0.2…1 mm² (AWG 24…AWG 14) flexible with cable end Control circuit: connector 2 cable(s) 0.2…1.5 mm² (AWG 24…AWG 14) flexible without cable end Control circuit: connector 2 cable(s) 0.5…1.5 mm² (AWG 24…AWG 14) flexible without cable end Control circuit: connector 2 cable(s) 0.2…1 mm² (AWG 24…AWG 14) solid without cable end |
tightening torque |
Control circuit: 0.5…0.6 N.m flat screwdriver 3 mm
|
pollution degree |
3
|
electromagnetic compatibility |
Electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2
Radiated RF fields, 3, 10 V/m, conforming to EN/IEC 61000-4-3 Fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4 Fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4 Voltage dips and interruptions immunity test, 70 %, 500 ms, conforming to EN/IEC 61000-4-11 Conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6 Temperature sensor: surges (serial mode), 0.5 kV, conforming to EN/IEC 61000-4-5 Temperature sensor: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5 Control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5 Control circuit: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5 Communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 Relay outputs and supply: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5 Relay outputs and supply: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5 |
width |
91 mm
|
height |
61 mm
|
depth |
122.5 mm
|
net weight |
0.53 kg
|
web services |
Web server
|
compatibility code |
LTMR
|
standards |
IACS E10
UL 508 CSA C22.2 No 14 EN 60947-4-1 IEC 60947-4-1 |
---|---|
product certifications |
CCC
ABS C-Tick NOM CSA RMRoS RINA UL BV KERI DNV GL EAC LROS (Lloyds register of shipping) ATEX |
protective treatment |
12 x 24 hour cycles conforming to EN/IEC 60068-2-30
48 h conforming to EN/IEC 60070-2-11 TH conforming to EN/IEC 60068 |
fire resistance |
650 °C conforming to EN/IEC 60695-2-12
960 °C conforming to UL 94 |
ambient air temperature for operation |
-20…60 °C
|
ambient air temperature for storage |
-40…80 °C
|
operating altitude |
<= 2000 m without derating
|
mechanical robustness |
Vibrations mounted on symmetrical rail: 1 Gn, 5…300 Hz conforming to EN/IEC 60068-2-6
Vibrations plate mounted: 4 Gn, 5…300 Hz conforming to EN/IEC 60068-2-6 Shocks half sine wave acceleration: 15 Gn for 11 ms conforming to EN/IEC 60068-2-27 |
IP degree of protection |
IP20
|