LTMR08EBD Motor controller LTMR TeSys T – 24 V DC 8 A for Ethernet TCP/IP

Category:

LTMR08EBD Motor controller LTMR TeSys T – 24 V DC 8 A for Ethernet TCP/IP

Specification:

range
TeSys
product name
TeSys T
device short name
LTMR
product or component type
Motor controller
device application
Equipment monitoring and control
measurement current
0.4…8 A
[Us] rated supply voltage
24 V DC
current consumption
56…127 mA
supply voltage limits
20.4…26.24 V DC
communication port protocol
Modbus TCP/EtherNet/IP
bus type
Ethernet IEEE 802.3 interface, addressing 0…159, transmission rate 10…100 Mbit/s, RJ45 with 2 shielded twisted pairs
[Ui] rated insulation voltage
690 V conforming to EN/IEC 60947-1
690 V conforming to CSA C22.2 No 14
690 V conforming to UL 508
[Uimp] rated impulse withstand voltage
6 kV current or voltage measurement circuit conforming to EN/IEC 60947-4-1
0.8 kV communication circuit conforming to EN/IEC 60947-4-1
0.8 kV supply, inputs and outputs conforming to EN/IEC 60947-4-1
short-circuit withstand
100 kA conforming to EN/IEC 60947-4-1
associated fuse rating
4 A gG for output
0.5 A gG for control circuit
protection type
Phase failure
Locked rotor
Earth-leakage protection
Thermal protection
Overload
Phase unbalance
Reverse polarity protection
Power factor variation
Overload (long time)
Thermal overload protection
Load fluctuation
network and machine diagnosis type
Event recording
Remaining operating time before overload tripping
Trip context information
Waiting time after overload tripping
Running hours counter/operating time
Trip history information
Fault recording
Starting current and time
Phase fault and earth fault trip counters
Motor control command recording
logic input number
6
input current
7 mA
current state 0 guaranteed
Logic input: < 5 V and <= 15 mA for 5 ms
current state 1 guaranteed
Logic input: < 15 V and 2…15 mA for 15 ms
maximum output switching frequency
2 Hz
load current
5 A at 250 V AC for logic output
5 A at 30 V DC for logic output
permissible power
480 VA (AC-15), Ie = 2 A, 500000 cycles (output)
30 W (DC-13), Ie = 1.25 A, 500000 cycles (output)
maximum operating rate
1800 cyc/h
contacts type and composition
1 NO + 1 NC fault signal
3 NO
metering type
Average current Iavg
Temperature
Earth-fault current
Phase current I1, I2, I3 RMS
Imbalance current
measurement accuracy
5…15 % earth fault current internal measurement (for current > 0.1 A)
1 % voltage (100…830 V)
3 % power factor (cos φ > 0.6)
5 % earth fault current external measurement (< 5 % or 0.01 A)
+/- 30 min/year internal clock
0,02 temperature
1 % current
5 % active and reactive power
overvoltage category
III
connection pitch
5.08 mm
connections – terminals
Control circuit: connector 1 cable(s) 0.25…2.5 mm² (AWG 24…AWG 14) flexible with cable end
Control circuit: connector 1 cable(s) 0.2…2.5 mm² (AWG 24…AWG 14) flexible without cable end
Control circuit: connector 1 cable(s) 0.25…2.5 mm² (AWG 24…AWG 14) flexible without cable end
Control circuit: connector 1 cable(s) 0.2…2.5 mm² (AWG 24…AWG 14) solid without cable end
Control circuit: connector 2 cable(s) 0.2…1 mm² (AWG 24…AWG 14) flexible with cable end
Control circuit: connector 2 cable(s) 0.2…1.5 mm² (AWG 24…AWG 14) flexible without cable end
Control circuit: connector 2 cable(s) 0.5…1.5 mm² (AWG 24…AWG 14) flexible without cable end
Control circuit: connector 2 cable(s) 0.2…1 mm² (AWG 24…AWG 14) solid without cable end
tightening torque
Control circuit: 0.5…0.6 N.m flat screwdriver 3 mm
pollution degree
3
electromagnetic compatibility
Electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2
Radiated RF fields, 3, 10 V/m, conforming to EN/IEC 61000-4-3
Fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4
Fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4
Voltage dips and interruptions immunity test, 70 %, 500 ms, conforming to EN/IEC 61000-4-11
Conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6
Temperature sensor: surges (serial mode), 0.5 kV, conforming to EN/IEC 61000-4-5
Temperature sensor: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5
Control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5
Control circuit: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5
Communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5
Relay outputs and supply: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5
Relay outputs and supply: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5
width
91 mm
height
61 mm
depth
122.5 mm
net weight
0.53 kg
web services
Web server
compatibility code
LTMR
standards
IACS E10
UL 508
CSA C22.2 No 14
EN 60947-4-1
IEC 60947-4-1
product certifications
CCC
ABS
C-Tick
NOM
CSA
RMRoS
RINA
UL
BV
KERI
DNV
GL
EAC
LROS (Lloyds register of shipping)
ATEX
protective treatment
12 x 24 hour cycles conforming to EN/IEC 60068-2-30
48 h conforming to EN/IEC 60070-2-11
TH conforming to EN/IEC 60068
fire resistance
650 °C conforming to EN/IEC 60695-2-12
960 °C conforming to UL 94
ambient air temperature for operation
-20…60 °C
ambient air temperature for storage
-40…80 °C
operating altitude
<= 2000 m without derating
mechanical robustness
Vibrations mounted on symmetrical rail: 1 Gn, 5…300 Hz conforming to EN/IEC 60068-2-6
Vibrations plate mounted: 4 Gn, 5…300 Hz conforming to EN/IEC 60068-2-6
Shocks half sine wave acceleration: 15 Gn for 11 ms conforming to EN/IEC 60068-2-27
IP degree of protection
IP20