Specification:
| range | TeSys |
|---|---|
| product name | TeSys GV2 |
| device short name | GV2P |
| device application | Motor |
| trip unit technology | Thermal-magnetic |
| poles description | 3P |
|---|---|
| network type | AC |
| utilisation category | AC-3 IEC 60947-4-1 Category A IEC 60947-2 |
| network frequency | 50/60 Hz IEC 60947-4-1 |
| fixing mode | 35 mm symmetrical DIN rail clipped Panel screwed with 2 x M4 screws) |
| operating position | Any position |
| motor power kW | 1.1 kW 400/415 V AC 50/60 Hz 1.5 kW 500 V AC 50/60 Hz 2.2 kW 690 V AC 50/60 Hz |
| breaking capacity | 100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 100 kA Icu 440 V AC 50/60 Hz IEC 60947-2 100 kA Icu 500 V AC 50/60 Hz IEC 60947-2 8 kA Icu 690 V AC 50/60 Hz IEC 60947-2 |
| [Ics] rated service short-circuit breaking capacity | 100 % 690 V AC 50/60 Hz IEC 60947-2 100 % 500 V AC 50/60 Hz IEC 60947-2 100 % 230/240 V AC 50/60 Hz IEC 60947-2 100 % 440 V AC 50/60 Hz IEC 60947-2 100 % 400/415 V AC 50/60 Hz IEC 60947-2 |
| control type | Rotary knob |
| Line Rated Current | 4 A |
| thermal protection adjustment range | 2.5…4 A |
| magnetic tripping current | 51 A |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz IEC 60947-2 |
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz IEC 60947-2 |
| [Ith] conventional free air thermal current | 4 A IEC 60947-4-1 |
| [Uimp] rated impulse withstand voltage | 6 kV IEC 60947-2 |
| power dissipation per pole | 2.5 W |
| mechanical durability | 100000 cycles |
| electrical durability | 100000 cycles AC-3 440 V |
| maximum operating rate | 25 cyc/h |
| rated duty | Continuous IEC 60947-4-1 |
| connections – terminals | screw clamp terminals 2 0.00…0.01 in² (1…6 mm²) solid screw clamp terminals 2 0.00…0.01 in² (1.5…6 mm²) flexible without cable end screw clamp terminals 2 0.00…0.01 in² (1…4 mm²) flexible with cable end |
| tightening torque | 15.05 lbf.in (1.7 N.m) screw clamp terminals |
| suitability for isolation | Yes IEC 60947-1 |
| phase failure sensitivity | Yes IEC 60947-4-1 |
| height | 3.50 in (89 mm) |
| width | 1.77 in (45 mm) |
| depth | 3.82 in (97 mm) |
| standards | EN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 |
|---|---|
| product certifications | IECEE CB Scheme UL CSA CCC EAC ATEX BV LROS (Lloyds register of shipping) DNV-GL RINA |
| protective treatment | TH |
| IP degree of protection | IP20 IEC 60529 |
| IK degree of protection | IK04 |
| ambient air temperature for operation | -4…140 °F (-20…60 °C) |
| ambient air temperature for storage | -40…176 °F (-40…80 °C) |
| fire resistance | 1760 °F (960 °C) IEC 60695-2-1 |
| operating altitude | 6561.68 ft (2000 m) |